Fire Alarm System Wiring and Installation Requirements

10.6.2 Wiring Installation Requirements

The following requirements shall be met for wiring installation:

10.6.2.1 Conductor Specifications

All conductors shall be a minimum of #16 gauge solid copper, type THHN, THWN, or TFN. All wiring shall be run continuously from device to device.

10.6.2.2 Circuit Separation

The minimum separation between outgoing and return circuits shall be a minimum of one foot vertically and four feet horizontally, in accordance with the provisions of NFPA-72 6.4.2.2.2.

10.6.2.3 Cable Cutting

A cable-cutting tool with a controlled depth of cut shall be used in all MC cable installations.

10.6.2.4 MC Cable Connectors

UL-listed type MC cable connectors with insulated bushings and screw-type cable attachments shall be used in all MC cable installations. Connectors shall be steel, not the cast type.

10.6.2.5 Conductor Size and Voltage Drop

Conductor size shall be increased as required to limit voltage drop to a maximum of three percent.

10.6.2.6 Initiating Device and Notification Appliance Support

All initiating devices and notification appliances shall be supported independently of their attachment to the circuit conductor.

10.6.3 Fire Alarm System Conductor Color Code

The following color code shall be used for all fire alarm system conductors:

10.6.3.1 Initiating Device Circuit (IDC/SLC)

Red and black. Red shall be positive and black shall be negative.

10.6.3.2 Notification Appliance Circuit (NAC)

Blue and white. Blue shall be positive and white shall be negative. When bells, chimes, or other audible/visual devices are used in lieu of horns, this color code shall be followed.

10.6.3.3 Flashing Strobe Circuit

If a separate feed is required, it shall be blue and white. Blue shall be positive and white shall be negative.

10.6.3.4 Sprinkler/Standpipe Circuits

Red and black. Red shall be positive and black shall be negative.

10.6.3.5 Smoke Detector Circuits

If a separate power feed is required, it shall be brown and violet. Violet shall be positive and brown shall be negative.

10.6.3.6 Auxiliary Remote Power Supply Circuits

Brown and violet. Violet shall be positive and brown shall be negative.

10.6.3.7 Electro-Magnetic Door Holdback Circuits

Gray and gray.

10.6.3.8 Municipal Master Box Tripping Circuits

Orange and orange. Conductors for this circuit shall be installed in a separate raceway.

10.6.3.9 Elevator Capture Circuits

Brown and yellow.

10.6.3.10 HVAC Shutdown Circuits

Orange and yellow.

10.6.3.11 Remote Annunciator Circuits

Violet and numbered at each end.

10.6.3.12 Bond Wires

Bond wires from the control panel to the master box ground rod, and all requiring bonding conductors, shall be green or bare.

10.6.3.13 Municipal Fire Alarm Loop

Black and white.

10.6.3.14 AC Supply Circuit

White, black, and red. Black shall be one phase and red shall be the opposite phase, if required. White shall be neutral. If a separate feed for the battery is required, it shall be black and white unless the main fire alarm control unit requires only one AC feed. In that case, the conductors to the battery charger should be red and white.

10.6.4 Primary AC Power and Battery Charger Circuits

Primary AC power and/or battery charger circuits shall be on dedicated branch circuits. Circuit breaker locks shall be provided and listed for use with the applicable circuit breaker. The location of the circuit disconnecting means shall be permanently identified at the fire alarm control unit. AC and DC portions of the system shall be installed in separate raceways. [NFPA 72 4.4.1]

10.6.5 Fire Alarm Wiring and Terminal Cabinets

Any fire alarm wiring between the fire alarm control unit and remote terminal cabinets, or between remote terminal cabinets, may, at the option of the installer, be a multi-conductor cable with each conductor numbered at two-inch intervals. All wiring from terminal cabinets to alarm devices shall conform to the color code specified above. Terminal cabinets with hinged, lockable red covers shall be provided at all junction points. All conductor splices or terminations shall be made on screw-type terminal blocks. Wire nuts, butt, or crimp-type connectors shall not be used. All terminals within a terminal cabinet shall be properly labeled.

10.6.6 Heat and Smoke Detector Spacing

Spacing and location of heat detectors or smoke detectors required by this Code shall be in accordance with NFPA 72.

10.6.7 Smoke Detector Installation and Cleaning

Smoke detectors shall not be installed until after the construction clean-up of all trades is complete and final. Detectors that have been installed prior to final clean-up by all trades shall be cleaned or replaced per NFPA 72, Inspection, Testing, and Maintenance. [NFPA 72 5.7.1.11]